The modbus node

Deprecated since version 0.19.7, use the modbus_read instead.


Read data via modbus tcp, supported read functions are : ['coils', 'hregs', 'iregs', 'inputs', 'memory']

Reading can be done periodically (if every is given) and/or via a trigger (incoming value).

Read multiple values with possibly different functions at once.

The node will optimize reading by treating contiguous values as one reading var. Normally the node will open one connection for every variable (after read optimization is applied). The maximum number of connections can be set with the max_connections option.

If the align property is set, the nodes's read times will be truncated to the every property (For example, if the node is started at 12:06 and the every property is 5m then the next read will occur at 12:10, then the next at 12:15 and so on, instead of 12:06, 12:11 and so on).

Examples

|modbus()
.ip('127.0.0.1') 
.device(255)
.every(1s)
.function('coils', 'hregs', 'iregs', 'hregs')
.from(2127, 3008, 104, 30306)
.count(1, 2, 2, 4)
.as('data.EnergyConsumption', 'data.CurrentValue', 'data.EnergyDelivered')
.output('int16', 'float32', 'float32', 'double')
.signed(true, true, false, false) 
|modbus()
.ip('127.0.0.1')  
.every(2m)
.function('hregs', 'hregs', 'hregs')
.from(2127, 2125, 104)
.count(2, 2, 2)
.as('data.EnergyConsumption', 'data.CurrentValue', 'data.EnergyDelivered')
.output('float32', 'float32', 'float32') 

The above modbus node will open 2 connections to the given modbus device, because the start values 2125 (2 bytes) and 2127 (2 bytes) can be treated as one single value.

Parameters

Parameter Description Default
ip( string ) ip address of modbus device
port( integer ) port of modbus device 502
every( duration ) time between reads undefined
align( is_set ) align read intervals according to every false (not set)
device( integer ) modbus device id (0-255) 255
function( string_list ) list of read functions, one of ['coils', 'hregs', 'iregs', 'inputs', 'memory']
from( integer_list ) list of start values
count( integer_list) list of count values, how much data to read for every function given
as( string_list ) output names for the read values
output( string_list ) list of output formats one of ['int16', 'int32', 'float32', 'double', 'coils', 'ascii', 'binary'] undefined
signed( atom_list true/false) list of values indicating if values are signed undefined
round( integer ) Round all float32 and double values with the given precision. If a value has less than the given decimal places, it will be left untouched undefined (no rounding)
max_connections( integer ) number of connections to the modbus device auto, meaning 1 connection for every variable (after read optimization)

Note that, if given, all read parameters(function, from, count, as, output, signed) must have the same length, this means if you have two values you want to read :

.function('coils', 'hregs')` 

all corresponding read params (if given) must have the same length:

.as('val1', 'val2')
.output(int16, float32)
.from(1,2) 
.count(2,4)
.signed(true, true)